Maintenance
Continuous Feed: 2 – 5 ppm BCP 1030
Slug Dose: 12 – 30 ppm BCP 1030
- Dose 1 to 3 times per week.
- Optimize the dosing and frequency of dosing based on quality control (QC) metrics.
Clean-Up
Slug Dose: 13 – 50 ppm BCP 1030
- Dose each day or until system performance measurements and visual inspection show satisfactory removal of organic deposits and system clean-up.
Super Slug Dose (Clean-up of heavily fouled systems): 50 ppm BCP 1030
- Dose at 1-2 hour intervals.
- Add high concentration dose (50 ppm) of BCP 1030 to penetrate and disperse
organic deposits from the surfaces. - After 1-2 hours, initiate an enhanced/manual blow down to remove released organic
deposits & non-organic deposits. - Repeat dose and enhanced/manual blow down steps until system quality control
measurements indicate satisfactory clean up.